医用直线加速器超限混凝土结构施工技术
2020-09-01
来源:爱问旅游网
技术园地 echnical Scope 2014年第32卷第7期 医用直线加速器超限混凝土结构施工技术 王士超,谢益庭,孙 雷 (中国新兴建设开发总公司,北京100039) 【摘要】某医院病房大楼工程总建筑面积约18.8万m ,直线加速器室楼板及墙梁为超限混凝土,通过实行优化混凝土配合 比、保证混凝土连续供应、严格浇筑顺序、加强混凝土养护等措施,使直线加速器混凝土浇筑期间未发生安全事故,为以后的施 工提供借鉴。 【关键词】直线加速器;混凝土;超限;裂缝;稳定 【中图分类-g-I TU755 【文献标志码】B 【文章编号】1671-3702(2014)07--0045--03 Construction Technology of Overrun Concrete Structure for Medica1 Linear Accelerator WANGShichao.XIE Yiting,SUN Lei (Xinxing construction and development general company,Beij'ing 100039,China J Abstract:The total area of a hospital ward building is 188 000 m 。The floor,wall and beam of the room for 1inear accelerator are exceed limit concrete structure.Adopt the measures of optimize concrete ratio, insure Concrete supply continuously,strict casting order,enhance concrete curing,there are no safety accidence occurred during concrete pouring for linear accelerator,and provide experience for the later project. Keywords:1/near accelerator;concrete:exceed limit:crack:stability 1工程概况 某医院病房大楼工程由外科楼、内科楼及转化医 学楼3部分组成,东西长149 m、南北宽127 m,总建筑面 质量,防止混凝土出现裂缝,确保模板架体安全、稳定。 3技术方案设计 3.1模板及支撑系统材料选择 1)模板:采用1 830 mm ̄915 mmX15 mm厚胶 合板; 积约18.8万m。:地下2层,地上18层,檐高84.45 m。 地下2层在(2—22)一(2—23)~(2~25)~(2— 26)/(2—1/s)~(2—J)一(2一G)轴范围为直线加速器室, 2)木方:采用100 mrn ̄100 mm松木; 3)方钢:采用50 mm ̄50 mm ̄3 mm方钢管; 层高6.10 m,楼板厚1 300 mlil,墙顶暗梁截面为(1 100 —1 950)mm×1 300 mlTl,最大截面为2 600 mm 4)螺栓:梁侧采用M12对拉螺栓; 5)支撑系统:选用 48 mrn ̄3.5 mm钢管及其配 ×1 300mm 2施工重点 保证直线加速器室墙体、梁板大体积混凝土施工 作者简介:王士超,男,工程师,项目经理,研究方向为建筑工程结 构、装饰及幕墙。 件;梁板支撑除直线加速器范围和层高7.95 m处采用扣 件式架子管外,其余部位均采用碗扣架: 6)纵横向剪刀撑:选用q548 mm ̄3.5 mm钢管及其 配件: 7)垫板:采用脚手架配套底托,垫板为200 mm ̄ 一45—